Description and application
Electric cable for mine interiors, with insulation and PVC sheath. Nominal voltage 0.6/1kV For applications where the cable is subjected to very high mechanical loads in dry and humid areas, outdoors and in areas with danger of explosion, especially in mining and industry, quarries and construction sites.
-
Markets
-
LocationIndoors/Outdoors
-
Type of installationFlexible
Design
-
ArmouringGalvanised steel and copper wire core, conductance equivalent to the protective conductor. Steel strap counter-spiral.
- ConductorPolished copper, Class 1 ≤ 4 mm², Class 2 > 6 mm² according to IEC/EN 60228
- InsulationType B PVC
- IdentificationYellow, green, brown
- GripType ST2 PVC
- Grip colourYellow or black
- SheathPVC
- ColourYellow or black
Technical characteristics
-
Service temperature in fixed and protected installation-15 °C to +80 °C
-
Service voltage0.6/1kV
- Temperature during handling, transport and storage+5 °C to +50 °C
- Test voltage3.500 V
- Minimum bend radius in fixed installation10 x outer diameter
Other properties
- Standards of referenceUNE 22510 & UNE 22511
- Water resistanceAD5 Jets (possibility of water jets from any direction)
- Impact resistanceAG4 Very strong (reinforced for severe industrial use)
- UV resistanceGood (possibility of sheath discolouration over long time)
- Chemical resistance in generalPlease refer to technical appendix
- RoHSFree of harmful substances according to RoHS II - Directive 2011/65/EU and Delegated Directive (EU) 2015/863 amending Annex II of Directive 2011/65/EU
Fire resistant properties
- Flame retardantEN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2, NFC 32070 C2
Other colours and configurations possible on request. Sumcab Specialcable Group S.L. (Sumcab) reserves the right to make changes to the product described in this specification without prior notice.While Sumcab makes every reasonable effort to ensure the accuracy of the data at the time of this publication, the information and specifications described in this document are subject to errors or omissions. Sumcab assumes no responsibility that may arise from the use of this specification. Drawings are not to scale unless otherwise specified and are provided for general and informational purposes only. All values represented in this specification should be used only as a guide.
Do you need some help?
Get in touch and we will get back to you as quickly as possible.
+34 93 381 78 76