Description and application
Flexible armoured instrumentation cable, foiled as a whole, halogen-free insulation and sheath. For the transmission of signals between equipment in industrial facilities in locations with hazardous atmospheres according to ITC-BT-029 (ATEX)
-
Markets
-
LocationIndoors/Outdoors
-
Type of installationFixed
Design
-
Overall cable shieldAluminium/polyester tape with 100% coverage + tinned copper drain wire.
-
ArmouringGalvanized steel wire core
- ConductorBare copper wires, flexible, Class 5 to IEC 60228
- InsulationPolyolefin
- WiringTwo conductors form a twisted pair with optimum pitch to minimise potential external interference that can disrupt the signal. Pairs wired together concentrically.
- IdentificationNumbered black and blue
- GripPolyolefin
- Grip colourGreen
- SheathPolyolefin
- ColourGreen
Technical characteristics
-
Service temperature in fixed and protected installation-15 °C to +70 °C
-
Service voltage300/500 V
- Temperature during handling, transport and storage+5 °C to +50 °C
- Max. conductor temperature+70 °C
- Max. temperature in short circuit (max. 5 sec)+160 °C
- Test voltage2.000 V AC
- Minimum bend radius in fixed installation10 x outer diameter
Other properties
- Standards of referenceAccording to EN 50288-7
- Water resistanceAD5 Jets (possibility of water jets from any direction)
- Impact resistanceAG4 Very strong (reinforced for severe industrial use)
- Oil resistanceICEA S-73-532
- Resistance to hydrocarbonsICEA S-73-532 (4h, 70 ºC)
- Chemical resistance in generalPlease refer to technical appendix
- RoHSFree of harmful substances according to RoHS II - Directive 2011/65/EU and Delegated Directive (EU) 2015/863 amending Annex II of Directive 2011/65/EU
Fire resistant properties
-
Euroclase CPRCca- s1b, d1, a1
-
Halogen-freeEN 60754-1, IEC 60754-1, VDE 0482-754-1
- Fire requirementsEN 50575
- Flame retardantEN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2, NFC 32070 C2
- Fire retardantEN 50399 (for CPR version), EN 60332-3-24, IEC 60332-3-24, VDE 0482-332-3-24
- Low smoke opacityEN 61034-2 , IEC 61034-2, VDE 0482-1034-2
- Low gas corrosivityEN 60754-2, IEC 60754-2, VDE 0482-754-2
Other colours and configurations possible on request. Sumcab Specialcable Group S.L. (Sumcab) reserves the right to make changes to the product described in this specification without prior notice.While Sumcab makes every reasonable effort to ensure the accuracy of the data at the time of this publication, the information and specifications described in this document are subject to errors or omissions. Sumcab assumes no responsibility that may arise from the use of this specification. Drawings are not to scale unless otherwise specified and are provided for general and informational purposes only. All values represented in this specification should be used only as a guide.
Do you need some help?
Get in touch and we will get back to you as quickly as possible.
+34 93 381 78 76
Applications
Markets
Markets