Description and application

Flexible cable with anti-rodent sheath suitable for photovoltaic installations, both in mobile service and in fixed installation certified by TÜV and EN. Especially suitable for the connection between photovoltaic panels, and from the panels to the inverter from direct to alternating current.
  • Markets
  • Location
    Outdoors
  • Type of installation
    Fixed

Design

  • Conductor
    Tinned copper threads, flexible Class 5 according to EN 60228 and IEC 60228
  • Insulation
    Cross-link elastomer compound
  • Identification
    Colourless
  • Sheath
    Cross-linked polyolefin + anti rodent additive
  • Colour
    Black, red

Technical characteristics

  • Service temperature in fixed and protected installation
    -40 °C to +90 °C
  • Service voltage
    In direct current: 1,5/1,5 kV (1,8 kV), In alternate current: 1/1kV (1.2kV)
  • Service temperature in flexible installation
    -40 °C to +90 °C
  • Temperature during handling, transport and storage
    +5 °C to +50 °C
  • Max. conductor temperature
    +90 °C (+120 °C during 20.000 hrs)
  • Max. temperature in short circuit (max. 5 sec)
    +250 °C
  • Test voltage
    15kV, 6,5kV
  • Minimum bend radius in fixed installation
    4 x outer diameter
  • Minimum bend radius in flexible installation
    5 x outer diameter

Other properties

  • Standards of reference
    EN 50618
  • Certification
    TÜV 2 PFG 1169/ 08.07. Useful life 25 years at 90 °C
  • Water resistance
    AD8 Permanent Immersion (immersion equipment is permanently and fully covered)
  • Impact resistance
    AG2 Medium (industrial use)
  • Oil resistance
    Excellent
  • UV resistance
    Excellent
  • Chemical resistance in general
    Please refer to technical appendix
  • RoHS
    Free of harmful substances according to RoHS II - Directive 2011/65/EU and Delegated Directive (EU) 2015/863 amending Annex II of Directive 2011/65/EU

Fire resistant properties

  • Euroclase CPR
    Eca
  • Halogen-free
    EN 60754-1, IEC 60754-1, VDE 0482-754-1
  • Fire requirements
    EN 50575
  • Flame retardant
    EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2, NFC 32070 C2
  • Fire retardant
    EN 60332-3-24, IEC 60332-3-24, VDE 0482-332-3-24
  • Low smoke opacity
    EN 61034-2 , IEC 61034-2, VDE 0482-1034-2
  • Low gas corrosivity
    EN 60754-2, IEC 60754-2, VDE 0482-754-2

Other colours and configurations possible on request. Sumcab Specialcable Group S.L. (Sumcab) reserves the right to make changes to the product described in this specification without prior notice.While Sumcab makes every reasonable effort to ensure the accuracy of the data at the time of this publication, the information and specifications described in this document are subject to errors or omissions. Sumcab assumes no responsibility that may arise from the use of this specification. Drawings are not to scale unless otherwise specified and are provided for general and informational purposes only. All values represented in this specification should be used only as a guide.

Do you need some help?

Get in touch and we will get back to you as quickly as possible. 

 

+34 93 381 78 76

Applications

Markets

Markets