Description and application

Rigid instrument cable according to French standard NF M 87-202, foiled individually and as a whole, XLPE insulation and PVC sheath, fire retardant according to NF C 32-070 cat. C1. For the transmission of signals between equipment in industrial installations.
  • Featured benefits
    According to French regulations,
    Double Shield with 100% coverage,
    Excellent performance in case of fire,
    Blue colour for intrinsic safety circuits
  • Location
    Indoors/Outdoors
  • Type of installation
    Fixed

Design

  • Single shield
    Aluminium/polyester tape applied on each pair, with 100% coverage + tinned copper drain wire
  • Overall cable shield
    Aluminium/polyester tape with 100% coverage + tinned copper drain
  • Conductor
    Bare copper Class 1 IEC/EN60228 or 7 wires, rigid Class 2 IEC/EN60228
  • Insulation
    Polyolefin
  • Wiring
    Two conductors form a twisted pair with optimum pitch to minimise potential external interference that can disrupt the signal. Pairs wired together concentrically.
  • Identification
    Numbered red and white
  • Sheath
    Polyolefin
  • Colour
    Light blue

Technical characteristics

  • Service temperature in fixed and protected installation
    -15 °C to +70 °C
  • Service voltage
    500 V
  • Temperature during handling, transport and storage
    +5 °C to +50 °C
  • Max. conductor temperature
    +70 °C
  • Max. temperature in short circuit (max. 5 sec)
    +160 °C
  • Test voltage
    2.000 V AC
  • Minimum bend radius in fixed installation
    7.5 x outer diameter

Other properties

  • Standards of reference
    NF M 87-202 / IEC 60079-14 / EN 60079-14
  • Water resistance
    AD5 Jets (possibility of water jets from any direction)
  • Impact resistance
    AG2 Medium (industrial use)
  • Oil resistance
    NF M 87-202 Annex A &ANSI/ICEA S-73-532 (4h, 70 ºC)
  • Resistance to hydrocarbons
    NF M 87-202 Annex A &ANSI/ICEA S-73-532 (4h, 70 ºC)
  • UV resistance
    UL 1581 Section 1200
  • Chemical resistance in general
    Please refer to technical appendix
  • RoHS
    Free of harmful substances according to RoHS II - Directive 2011/65/EU and Delegated Directive (EU) 2015/863 amending Annex II of Directive 2011/65/EU

Fire resistant properties

  • Euroclase CPR
    Eca
  • Halogen-free
    EN 60754-1, IEC 60754-1, VDE 0482-754-1
  • Fire requirements
    EN 50575
  • Flame retardant
    EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2, NFC 32070 C2
  • Fire retardant
    NF C 32-070 cat C2 & IEC 60332-3-24, VDE 0482-332-3-24
  • Low smoke opacity
    EN 61034-2 , IEC 61034-2, VDE 0482-1034-2
  • Low gas corrosivity
    EN 60754-2, IEC 60754-2, VDE 0482-754-2

Other colours and configurations possible on request. Sumcab Specialcable Group S.L. (Sumcab) reserves the right to make changes to the product described in this specification without prior notice.While Sumcab makes every reasonable effort to ensure the accuracy of the data at the time of this publication, the information and specifications described in this document are subject to errors or omissions. Sumcab assumes no responsibility that may arise from the use of this specification. Drawings are not to scale unless otherwise specified and are provided for general and informational purposes only. All values represented in this specification should be used only as a guide.

Do you need some help?

Get in touch and we will get back to you as quickly as possible. 

 

+34 93 381 78 76