Description and application
Rigid instrument cable according to French standard NF M 87-202, foiled as a whole, XLPE insulation and PVC sheath, fire retardant NF C 32-070 cat C1. For the transmission of signals between equipment in industrial installations.
-
Featured benefitsAccording to French regulations,Shield with 100% coverage,Excellent performance in case of fire
-
LocationIndoors/Outdoors
-
Type of installationFixed
Design
-
Single shieldAluminium/polyester tape applied on each pair, with 100% coverage + tinned copper drain wire
-
Overall cable shieldAluminium/polyester tape with 100% coverage + tinned copper drain
- ConductorBare copper Class 1 IEC/EN60228 or 7 wires, rigid Class 2 IEC/EN60228
- InsulationPolyolefin
- WiringTwo conductors form a twisted pair with optimum pitch to minimise potential external interference that can disrupt the signal. Pairs wired together concentrically.
- IdentificationNumbered red and white
- SheathPolyolefin
- ColourGrey
Technical characteristics
-
Service temperature in fixed and protected installation-15 °C to +70 °C
-
Service voltage500 V
- Temperature during handling, transport and storage+5 °C to +50 °C
- Max. conductor temperature+70 °C
- Max. temperature in short circuit (max. 5 sec)+160 °C
- Test voltage2.000 V AC
- Minimum bend radius in fixed installation7.5 x outer diameter
Other properties
- Standards of referenceNF M 87-202
- Water resistanceAD5 Jets (possibility of water jets from any direction)
- Impact resistanceAG2 Medium (industrial use)
- Oil resistanceNF M 87-202 Annex A &ANSI/ICEA S-73-532 (4h, 70 ºC)
- Resistance to hydrocarbonsNF M 87-202 Annex A &ANSI/ICEA S-73-532 (4h, 70 ºC)
- UV resistanceUL 1581 Section 1200
- Chemical resistance in generalPlease refer to technical appendix
- RoHSFree of harmful substances according to RoHS II - Directive 2011/65/EU and Delegated Directive (EU) 2015/863 amending Annex II of Directive 2011/65/EU
Fire resistant properties
-
Euroclase CPREca
-
Halogen-freeEN 60754-1, IEC 60754-1, VDE 0482-754-1
- Fire requirementsEN 50575
- Flame retardantEN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2, NFC 32070 C2
- Fire retardantNF C 32-070 cat C2 & IEC 60332-3-24, VDE 0482-332-3-24
- Low smoke opacityEN 61034-2 , IEC 61034-2, VDE 0482-1034-2
- Low gas corrosivityEN 60754-2, IEC 60754-2, VDE 0482-754-2
Other colours and configurations possible on request. Sumcab Specialcable Group S.L. (Sumcab) reserves the right to make changes to the product described in this specification without prior notice.While Sumcab makes every reasonable effort to ensure the accuracy of the data at the time of this publication, the information and specifications described in this document are subject to errors or omissions. Sumcab assumes no responsibility that may arise from the use of this specification. Drawings are not to scale unless otherwise specified and are provided for general and informational purposes only. All values represented in this specification should be used only as a guide.