Description and application

Flexible cable for mine interiors, Asymmetric. For applications where the cable is subjected to very high mechanical loads in dry and humid areas, outdoors and in areas with danger of explosion, especially in mining and industry, quarries and construction sites.

Design

  • Conductor
    Tinned copper threads, flexible Class 5 according to EN 60228 and IEC 60228
  • Insulation
    EPR (+ semiconductor shield on each phase conductor)
  • Identification
    Phases in brown, black, grey. Blue pilot, black, black
  • Grip
    Rubber compound
  • Grip colour
    Natural
  • Sheath
    Rubber
  • Colour
    Yellow

Technical characteristics

  • Service temperature in fixed and protected installation
    -20 °C to +85 °C
  • Service voltage
    0.6/1kV
  • Service temperature in flexible installation
    -5 °C to +85 °C
  • Temperature during handling, transport and storage
    +5 °C to +50 °C
  • Max. conductor temperature
    90°C
  • Max. temperature in short circuit (max. 5 sec)
    250°C
  • Test voltage
    3.500 V
  • Minimum bend radius in fixed installation
    4 x outer diameter
  • Minimum bend radius in flexible installation
    7.5 x outer diameter

Other properties

  • Standards of reference
    UNE 22510 & UNE 22513
  • Water resistance
    AD5 Jets (possibility of water jets from any direction)
  • Impact resistance
    AG4 Very strong (reinforced for severe industrial use)
  • Oil resistance
    EN 60811-2-1
  • UV resistance
    Good (possibility of sheath discolouration over long time)
  • Chemical resistance in general
    Please refer to technical appendix
  • RoHS
    Free of harmful substances according to RoHS II - Directive 2011/65/EU and Delegated Directive (EU) 2015/863 amending Annex II of Directive 2011/65/EU

Fire resistant properties

  • Flame retardant
    EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2, NFC 32070 C2

Other colours and configurations possible on request. Sumcab Specialcable Group S.L. (Sumcab) reserves the right to make changes to the product described in this specification without prior notice.While Sumcab makes every reasonable effort to ensure the accuracy of the data at the time of this publication, the information and specifications described in this document are subject to errors or omissions. Sumcab assumes no responsibility that may arise from the use of this specification. Drawings are not to scale unless otherwise specified and are provided for general and informational purposes only. All values represented in this specification should be used only as a guide.