Description and application

Cable for Foundation Field Bus communication for fixed installation, PVC sheath. Electromagnetic interference (EMI) protection.

Design

  • Overall cable shield
    Aluminium/polyester tape with 100% coverage + 0,50 mm² drain wire + tinned copper braid, 90% minimum coverage
  • Conductor
    Copper wires, multi-stranded
  • Insulation
    Special thermoplastic polymer
  • Identification
    Blue, brown (+ yellow/green in 2+1 model)
  • Sheath
    Low adhesion TPU (PUR)
  • Colour
    Yellow

Technical characteristics

  • Service temperature in fixed and protected installation
    -30 °C to +70 °C
  • Service voltage
    250 V (peaks)
  • Service temperature in flexible installation
    -5 °C to +50 °C
  • Temperature during handling, transport and storage
    +5 °C to +50 °C
  • Test voltage
    1.500 V AC
  • Impedance
    (31.25 KHz) 100 ± 20 Ohm
  • Capacity
    (1 KHz) ≈65 nF/km
  • Minimum bend radius in fixed installation
    7.5 x outer diameter

Other properties

  • Water resistance
    AD3 aerosols (possibility of water falling as a spray at an angle of up to 60°)
  • Oil resistance
    EN 60811-2-1
  • Chemical resistance in general
    Please refer to technical appendix
  • RoHS
    Free of harmful substances according to RoHS II - Directive 2011/65/EU and Delegated Directive (EU) 2015/863 amending Annex II of Directive 2011/65/EU
  • Paint-wetting impairment substances (PWIS)
    The materials used are free of silicone, cadmium and free of substances that prevent paint from gripping on surfaces

Fire resistant properties

  • Flame retardant
    EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2, NFC 32070 C2

Other colours and configurations possible on request. Sumcab Specialcable Group S.L. (Sumcab) reserves the right to make changes to the product described in this specification without prior notice.While Sumcab makes every reasonable effort to ensure the accuracy of the data at the time of this publication, the information and specifications described in this document are subject to errors or omissions. Sumcab assumes no responsibility that may arise from the use of this specification. Drawings are not to scale unless otherwise specified and are provided for general and informational purposes only. All values represented in this specification should be used only as a guide.

Do you need some help?

Get in touch and we will get back to you as quickly as possible. 

 