Description and application

Highly flexible shielded cable for powering engines in submersible pumps Electromagnetic interference (EMI) protection.
  • Location
    Indoors/Outdoors
  • Type of installation
    Fixed

Design

  • Overall cable shield
    Tinned copper braid
  • Conductor
    Bare copper wires, flexible, Class 5 to IEC 60228
  • Insulation
    HEPR
  • Identification
    ≤ 5 conductors
  • Sheath
    Rubber
  • Colour
    Black

Technical characteristics

  • Service temperature in fixed and protected installation
    -40 °C to +70 °C
  • Service voltage
    0.6/1kV
  • Service temperature in flexible installation
    -15 °C to +70 °C
  • Temperature during handling, transport and storage
    +5 °C to +50 °C
  • Max. conductor temperature
    +90 °C
  • Max. temperature in short circuit (max. 5 sec)
    +250 °C
  • Test voltage
    3.500 V
  • Minimum bend radius in fixed installation
    ≤ 25 mm = 4 x outer diameter. > 25 mm = 6 x outer diameter
  • Minimum bend radius in flexible installation
    ≤ 25 mm = 6 x outer diameter. > 25 mm = 8 x outer diameter

Other properties

  • Standards of reference
    EN 50525-2-21
  • Water resistance
    AD8 Permanent Immersion (immersion equipment is permanently and fully covered)
  • Impact resistance
    AG2 Medium (industrial use)
  • Oil resistance
    EN 60811-2-1
  • UV resistance
    UL 1581 Section 1200
  • Chemical resistance in general
    Please refer to technical appendix
  • RoHS
    Free of harmful substances according to RoHS II - Directive 2011/65/EU and Delegated Directive (EU) 2015/863 amending Annex II of Directive 2011/65/EU

Fire resistant properties

  • Flame retardant
    EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2, NFC 32070 C2

Other colours and configurations possible on request. Sumcab Specialcable Group S.L. (Sumcab) reserves the right to make changes to the product described in this specification without prior notice.While Sumcab makes every reasonable effort to ensure the accuracy of the data at the time of this publication, the information and specifications described in this document are subject to errors or omissions. Sumcab assumes no responsibility that may arise from the use of this specification. Drawings are not to scale unless otherwise specified and are provided for general and informational purposes only. All values represented in this specification should be used only as a guide.