Description and application

PVC flat cable, 750V, for electrical connection in lifts, elevators, forklifts and garlands. Maximum suspension of 35 m and travel speed of 1,6 m/second.
  • Location
    Indoors/Outdoors
  • Type of installation
    Flexible

Design

  • Conductor
    Bare copper wires, flexible, Class 5 to IEC 60228
  • Insulation
    PVC
  • Identification
    ≤ 5 conductors
  • Sheath
    PVC
  • Colour
    Black

Technical characteristics

  • Service temperature in fixed and protected installation
    -25 °C to +60 °C
  • Service voltage
    450/750 V
  • Service temperature in flexible installation
    -20 °C to +60 °C
  • Service temperature in mobile installation
    -20 °C to +60 °C
  • Temperature during handling, transport and storage
    +5 °C to +50 °C
  • Max. conductor temperature
    +70 °C
  • Max. temperature in short circuit (max. 5 sec)
    +160 °C
  • Test voltage
    2.500 V AC
  • Minimum bend radius in fixed installation
    4 x thickness
  • Minimum bend radius for mobile installation (free movement)
    5 x thickness
  • Minimum bend radius for festoon installation (Curtain/chain cable carrier)
    10 x thickness
  • Max. movement speed
    100 m/min. at 35 m max. height

Other properties

  • Standards of reference
    DIN VDE 0281 Part 404
  • Water resistance
    AD5 Jets (possibility of water jets from any direction)
  • Impact resistance
    AG2 Medium (industrial use)
  • Oil resistance
    EN 60811-2-1
  • UV resistance
    Good (possibility of sheath discolouration over long time)
  • Chemical resistance in general
    Please refer to technical appendix
  • RoHS
    Free of harmful substances according to RoHS II - Directive 2011/65/EU and Delegated Directive (EU) 2015/863 amending Annex II of Directive 2011/65/EU

Fire resistant properties

  • Flame retardant
    EN 60332-1-2, IEC 60332-1-2, VDE 0482-332-1-2, NFC 32070 C2

Other colours and configurations possible on request. Sumcab Specialcable Group S.L. (Sumcab) reserves the right to make changes to the product described in this specification without prior notice.While Sumcab makes every reasonable effort to ensure the accuracy of the data at the time of this publication, the information and specifications described in this document are subject to errors or omissions. Sumcab assumes no responsibility that may arise from the use of this specification. Drawings are not to scale unless otherwise specified and are provided for general and informational purposes only. All values represented in this specification should be used only as a guide.

Do you need some help?

Get in touch and we will get back to you as quickly as possible. 

 

+34 93 381 78 76